Why Use Buck-Boost Transformers?

The advantages of using a buck-boost transformer over an equivalent Standard Isolation Transformer are as follows:

Advantages

  • Used in a variety of applications
  • Inexpensive
  • Smaller and lighter
  • More efficient
  • 5-10 times increase in KVA

Disadvantages

  • No circuit isolation
  • Cannot create a neutral
  • KVA and voltages do not match what's on the nameplate KVA and voltages.

Buck-Boost Application

Buck-boost transformers offer an economical solution to the adjustment of line voltages that are slightly above or below normal. When a Buck-Boost transformer is connected as an autotransformer, only a portion of the load kVA is actually transformed. The majority of the load kVA is passed directly through to the source. For this reason a Buck-Boost transformer may be used to supply a much larger load kVA than is indicated on the nameplate. Buck-Boost transformers can be used to adjust stable voltages only. Fluctuating line voltages should be regulated with a line voltage conditioner.

  50 to 1000 VA 1500 to 5000 VA
UL Listed File: E50394 File: E50394
CSA Certified File: LR3902 File: LR3902
Frequency 50/60 Hz 50/60 Hz
Insulation System 130°C (80°C rise) 180°C (115°C rise)
Standard Design Single Phase, welded core construction made with high quality, high permeability silicon steel laminations. Computer designed coils, accurately wound from high quality copper magnetic wire. Single Phase, welded core construction made with high quality, high permeability silicon steel laminations. Computer designed coils, accurately wound from high quality copper magnetic wire.
Encapsulation All units from 50VA to 5kVA are encapsulated with electrical grade silica sand and resin compounds. All units from 50VA to 5kVA are encapsulated with electrical grade silica sand and resin compounds.
Enclosure Type Heavy Duty Encapsulated NEMA Type 3R (Optional NEMA 4, 4X & 12 Available) Heavy Duty Encapsulated NEMA Type 3R (optional NEMA 4, 4X and 12 available)
Enclosure Finish ANSI 61 Grey, UL50 ANSI 61 Grey, UL50
Termination Front accessible separate high and low voltage lead wires or copper tabs. Front accessible separate high and low voltage lead wires or copper tabs.
Conduit Knock-Outs Side and Rear standard on all units. Side and Rear standard on all units.
Mounting Standard Wall Mounting. Standard Wall Mounting.

Voltage Is the Key

Buck-Boost transformers represent an economical way to both raise supply voltage caused by line drop or equipment demand on the distribution system, or lower voltage caused by increased system voltages due to supply line adjustments. Some loads including lighting and resistive loads require a stable supply to maintain performance. The detrimental effects of incorrect supply line voltage can cause equipment failure. Buck-Boost transformers can correct line voltage within 5 to 25% of nominal.

Steps for Selecting Buck-Boost Transformers

The following information is required before selecting a buck-boost transformer:

  • Line Voltage - The voltage that you want to buck (decrease) or boost (increase). This can be determined by measuring the supply line voltage with a voltmeter.
  • Load Voltage - The voltage at which your equipment is designed to operate. This is listed on the nameplate of the load equipment.
  • Load kVA or Load Amps - You do not need to know both - one or the other is sufficient. This information usually can be found on the nameplate of the equipment that you want to operate. It is the sum of all the equipment that represents the load.
  • Frequency - The supply line frequency must be the same as the equipment to be operated - either 50 or 60 Hertz.
  • Phase - The supply line should be the same as the load - either single or three phase.

Four Steps to Select the Correct Buck-Boost Transformer

  • Select a "high voltage" and "low voltage" combination that is the closest to matching the high voltage and low voltage correction that is required for your application.
  • The kVA or current rating equal to, or greater than, the rating required by the total load. It is not likely that the exact value of the load will be found, so go to the next higher rating.
  • Select the corresponding catalog number of the exact buck-boost transformer required.
  • Connect the transformer in accordance with the connection diagram referenced where you selected your high voltage and low voltage combination.
Stock Check
Part No:
OR
Manufacturer:

Search Tips

Can't find a part number?
E-mail Us!

Leuze Sensors

The Product Spectrum encompasses familiar operating principles such as throughbeam photoelectric sensor, retro-reflective photoelectric sensor or scanner with background suppression. Due to their high performance reserve, these devices are used for reliable detection even with heavy soiling in category 3G and 3D applications. The temperature class for explosive gas areas is T4; for explosive dust areas it is 90°C.

Sola Power Supplies

The Metal Case reduces costs by eliminating separate enclosures. Quick change connectors simplify connectivity for distributed I/O devices on industrial machinery. This model provides 24 Vdc output with limited power to meet Class 2 requirements. Two models are currently offered based on application. The SCP100S24X-CP is designed for Control Power applications where a grounded power supply output is required.