NK Technologies has been manufacturing ground fault and residual current sensors for over two decades with a wide variety of models to suit specific applications.

With such a wide variety available, it can be complicated to select the appropriate model. We hope this short guide will help you navigate through the model selection. How large are the conductors feeding the monitored load?

NK Technologies AG Series Ground Fault Earth Leakage Sensors Distributors

Our ground fault sensors will not "see" any current under normal conditions, but all current carrying conductors must be able to pass through the sensing window. If the wires are #6 AWG or smaller, whether using two, three, or four wires, The AG Sensor will work. If larger wire is used, up to 300 MCM, The AGL Series will allow the wires to pass through the sensing window.

What will the sensor contact do in your control system? Since NK Technologies' sensors do not provide a circuit disconnect, they generally perform one of two functions: Close a circuit to energize a shunt trip breaker operating mechanism or, control the coil of a contactor (or relay).

Shunt trip operation: If the monitored load is less than 50 amps, we recommend the AG1-SDT1-120-DEN-030. The N.O. contact is used to close the circuit powering the shunt trip breaker accessory. This model uses nominal 120 VAC from a separate source for sensor power. The contacts return to the original state once the breaker opens and the fault is no longer detectable.

Contactor or relay operation: The same sensor, AG1, can be used to operate a contactor coil, but we recommend a latching output model to simplify the installation: AG1-NCR1-120-LA-030. This sensor will open the circuit powering the contactor coil and the contact will stay open until an external reset button is pressed.

A similar model number construction format is used for the larger AGL units, so shunt trip breaker applications would use AGL1-SDT1-120-DEN-030, and contactor applications would use the AGL1-NCR1-120-LA-030.

What is the power supply that will be used? If you do not have access to 120 VAC for power, NK Technologies offers sensors designed for 24 VAC or DC operation. Change "120" to "24U" in the model number.

Do you need a trip point higher or lower than 30 mA? Change the suffix in the model number from "030" to "005" (5 mA), up to 100 (100 mA). Higher still? Use AG2 (or AGL2) for trip points from 80 to 950 mA.

Would the application benefit from "fail-safe" contact action? This energizes the output relay as soon as power is applied to the sensor terminals. The contacts return to their original condition if power is removed from the sensor or a fault is detected. Change "DEN" to "ENE" in the model number. Fail-safe operation is not available with the latching output models.

Would a solid-state "contact" be preferred over a mechanical relay contact? We do offer them, but we suggest calling our factory technical support for guidance.

Need some time delay or an easily adjustable trip point? Take a look at the AGLD series for these features.

Need to monitor a primary circuit larger than 300 amps? Call the factory, and we will help with that too!

Auto Reset Model Contact Action

Model Contact Type No Power Control Power Applied - No Fault Control Power Applied - Fault
Normally De-energized (DEN or NF options) Normally Open Contact Open Open Closed
Normally Closed Contact Closed Closed Open
Normally Energized (ENE or FS options) Normally Open Contact Open Closed Open
Normally Closed Contact Closed Open Closed

Stock Check

Part No:
OR
Manufacturer:

Search Tips
Can't find a part number?
E-mail Us!

IDEC Relays

There is No Internal Wiring, which means no weak solder points and a completely lead-free manufacturing process. The contacts are cadmium-free as well, making the RU relays environmentally-friendly. All RU relays are also manufactured by a totally automated assembly process which means the relay is of the highest quality because the possibility of human error has been eliminated during the manufacturing process.

Panasonic Displays

The First SD Memory Card slot in the four-inch class allows for easy screen data transfer. A variety of other needs from manufacturing sites were also covered, including the connector location for efficient wiring, improved environmental resistance rated IP67, and newly designed bracket for more secure fastening. You can choose models with RS232C or RS422/485 interface, and the silver colored or black housing.