February 03, 2009
NK Transducers
The VTD Series
Voltage Transducers are high-performance transducers for sensing voltage in DC powered installations. Applicable for use on
circuits to 600 VDC, VTD voltage transducers provide a fully isolated, 4-20mA output proportional to rated nominal voltage in DC
circuits. Housed in a slim, compact, easy-to-install DIN-rail mount enclosure, the VTD Series comes in a variety of nominal
voltages.
|
Entrelec Monitors
The PLS Series
is a low cost phase sensitive control that provides an isolated contact closure when the proper A-B-C phase sequence is applied.
Protects sensitive 3 phase equipment and equipment operators from reverse rotation. Designed to be compatible with motor
overloads or other 3 phase equipment protection devices. Protection for equipment control centers where frequent reconnection or
electrical code
|
|
|
|
 |
(800) 894-0412 (208) 368-0415 (Fax) info@clrwtr.com |
|
SymCom, Inc. leads the industry in electronic motor control and protection. Under the brand names
MotorSaver and
PumpSaver, our products are designed to monitor the power
supply to protect single- and Three-Phase compressors, pumps and other motors from damaging power conditions such as high
voltage, low voltage, voltage unbalance, single-phasing, phase reversal, overcurrent, undercurrent, current unbalance and
ground fault. This includes pump underload and overload conditions more commonly referred to as dry-well, dead-head and
jammed-impeller.
If you are looking for SymCom Products, please call us at (800) 894-0412 or email us at
info@clrwtr.com we will do our best to help you
find the SymCom MotorSaver that you are looking for at the lowest prices possible. If you are searching for SymCom PumpSaver
technical information (data-sheets) please use the Technical Datasheets OR
Product Selection Guide page links.
|
|
I have a 777
or 77C product and every time the motor is shut off, the MotorSaver trips and flashes a
number alternating with run.
|
|
This is a normal condition. Every time the motor is shut off or the MotorSaver is power cycled, the
device goes through a rapid-cycle timer (programmed in RD1). This is to prevent the motor from being turned off and on
repeatedly in a short period of time. If you are using an alarm on the NC output contacts and do not wish the alarm to go
off every time the motor is turned off, set RD1 to 0. Keep in mind, though, this will disable rapid-cycle protection.
|
|
I have an LSR (Load Sensor) and I can't
get the relay contacts to energize.
|
|
The LSR will only energize its contacts if it sees current greater than the setpoint value. This
setpoint value can be 2-100A and is regulated using a 20-turn pot. For example, if you are only looking at 10A, the setpoint
screw needs to be turned several times counterclockwise until the setpoint is <10A, then the contacts will energize.
|
|
I have a 777 (or 77C or 601)
and when I try to change a setting, the number jumps back to the previously programmed value.
|
|
You have the Tamper Guard on. To unlock the Tamper Guard, turn the MODE SELECT dial to GF (OPT2 for a
77C, 4LFT for a 601). Push in and hold the RESET/PROGRAM button and turn the DISPLAY/PROGRAM dial clockwise until you see
"unL" on the display. Release the button. After changing the settings, you can lock the Tamper Guard by following the same
instructions except turn the dial until you see "Loc." This will prevent anyone from accidentally changing the
settings.
|
|
My 777 tripped on "ub." Is that current unbalance or voltage unbalance?
|
|
Current unbalance. Our devices will give a voltage unbalance reading at the initial power-up and will
prevent the motor from starting. Once the motor is running, a "ub" trip is due to a current unbalance.
|
|
My 777 displays current readings jumping around from 0 to 6A, but my clamp-on ammeter reads 3A (as an
example, numbers may vary).
|
|
The 777s will only read current above about 7A. You probably need to loop your conductors through the
holes a greater number of times (i.e. down through each round hole, back up through each rectangular hole, back down
through each round hole, etc.). Refer to the installation guide to review the setup procedure. Don't forget to reprogram
the MULT setting if you change the number of conductors through the unit.
|
|
I heard there's a high sensitivity mode for PumpSavers. How do I utilize this feature?
|
|
PumpSavers trip on an underload (dry-well) condition when the current drops below 80% of the
calibrated value. Sensitivity may be increased to 87% of the calibrated value.
|
|
Do I need fuses for the front end of my Voltage Monitor?
|
|
Please refer to SymCom's fusing considerations document. Fusing Application-Note
|
|
Do I need to turn the knob back to RESET on the PumpSaver to calibrate it?
|
|
No. To calibrate, simply turn the dial fully counter-clockwise to CAL while the pump is running under
normal conditions. The CAL light will be on for about 10 seconds. Once the pump turns off turn the dial out of the CAL
position (the pump will turn back on) and adjust to the desired restart delay setting. You're all set! The RESET position
has two functions:
- It can be used if the PumpSaver has tripped and is timing through its restart delay. Turn the dial to RESET, and
then back to the desired restart delay setting to restart the pump.
- It can also be used as a manual restart setting when automatic restarting is not desired.
|
|
Do I need to recalibrate the PumpSaver after a power loss?
|
|
No. The PumpSaver will remember the last calibrated values permanently.
|
|
My 777 tripped and reads "CF" on the display.
|
|
This Is A Contactor Failure Fault. This occurs when the
device sees a large current unbalance (>50%), but no voltage unbalance. Turn the MODE SELECT dial to VUB (voltage
unbalance) to check the setting. If it is high (>6%) set it to a lower number such as 6%. If there is a substantial
current unbalance along with a voltage unbalance, the unit will trip on single-phasing ("SP"), but will restart when
conditions improve and it times through restart delay programmed into RD2.
|
|
When do I need an HVR model version?
|
|
HVR products have a High Voltage Relay rated 480VA @ 600VAC pilot duty. These products can be used to
switch 480V controls (or 575V controls on a Model 350-600) when
No Control Power Transformer Is Used.
|
|
Can I use a 777-HVR with 240V controls?
|
|
Yes, but you must have 380-480VAC input voltage. It's not necessary to have the higher voltage relay,
but it will function the same.
|
|
|
|
|
 |
|
| Part Number: |
|
|
Can't find a part number?
E-mail Us! |
|
|