June 03, 2011
SSAC Monitors
The PLM Series
continuously measures the voltage of each of the three phases. The PLM Series uses a new microcontroller circuit design that
senses Undervoltage, Voltage Unbalance, Phase Loss, and Phase Reversal. Protection is assured when regenerated voltages are
present. Both Delta and Wye systems can be monitored; no connection to neutral is required.
|
NK Power Monitors
APMR Series Power Monitoring Relays
are intended for sensing true, active power and measuring KW on 1O or 3O applications. Applicable on nominal circuits of 120,
240, and 480VAC, the APMR offers multiple relay outputs adjustable to trip when desired power thresholds are reached. As an
added benefit, a fully isolated 4-20mA output proportional to sensed KW is standard. All trip points and associated time
delays are
|
|
|
|
 |
(800) 894-0412 (208) 368-0415 (Fax) info@clrwtr.com |
 Model 80 |
SymCom Model 80 is designed to continuously monitor phase rotation of 3-phase systems. Critical
applications include fan motors, scroll compressors, grinders, conveyor systems, elevators and escalators.
A solid-state sensing circuit drives an internal electro-mechanical relay which is energized when proper
phase rotation is applied. An LED indicator illuminates when phase rotation is correct. Reset is automatic.
|
|
If you are looking for SymCom Three-Phase Voltage Monitors, please call us on
(800) 894 - 0412 or email us at
info@clrwtr.com
we will do our best to help you find the SymCom Motor Protectors that you are looking for at the most competitive prices
possible. If you are searching for SymCom Microcontroller Based Voltage Monitor technical information (data-sheets) please
use the datasheets or product selection guide page links.
|
 Model 102A |
SymCom Model 102A is an auto-ranging voltage monitor designed to protect 3-phase motors regardless of size.
It is used on 190-480VAC, 50 or 60Hz motors to prevent damage caused by incoming power problems. A unique
microcontroller-based voltage and phase-sensing circuit constantly monitors the 3-phase voltages to detect harmful power line
conditions. When a harmful condition is detected, the MotorSaver's output relay is deactivated after a specified trip delay.
The output relay reactivates after power line conditions return to acceptable levels. The Model 102A includes advanced single
LED diagnostics. Five different light patterns distinguish between faults and normal conditions.
|
 Model 102-600 |
The Model 102-600 is a voltage monitor designed to protect 3-phase, 475-600VAC, 50/60Hz motors from damage
caused by low voltage, voltage unbalance, single phasing, and phase reversal. A unique microcontroller-based voltage sensing
circuit constantly monitors the single-phase voltages to detect harmful power line conditions. When a harmful condition is
detected, the102-600's output relay is deactivated after a fixed trip delay. The output relay reactivates after power line
conditions return to an acceptable level and a fixed amount of time has elapsed (restart delay). The trip delay prevents
nuisance tripping due to rapidly fluctuating power line conditions.
|
 Model 102LG |
SymCom Model 102LG is a line to ground voltage monitor. It is used on 190-480VAC, 50 to
60Hz motors to prevent damage caused by low voltage conditions from line to ground.
|
 Model 201A |
SymCom The Model 201A is an auto-ranging voltage monitor designed to protect 3-phase
motors regardless of size. It is used on 190-480VAC, 50 or 60Hz motors to prevent damage caused by incoming power problems.
- Protects 3-phase motors from:
- Low voltage
- Single-phase
- Reverse-phase
- Voltage unbalance
- Diagnostic LED
- Optional high voltage protection
- UL Listed
- CE compliant
- 8-pin plug in; DIN rail or surface mount
- Convenient for areas with limited space
|
 Model 201A-AU |
SymCom Model 201A-AU is the newest, most versatile, plug-in style voltage monitor designed
to protect 3-phase motors from damaging power conditions. Its wide operating range combined with UL, cUL and CE compliance
enables quick access to domestic and global markets. The Model 201A-AU automatically senses whether it is connected to a
190-240V, 60Hz system, a 440-480V, 60Hz system, or a 380-416V, 50Hz system. An adjustment is provided to set the nominal line
voltage from 190-240 or 380-480VAC. Other variable settings include a 1-30 second trip delay, manual or 1-500 second restart
delay, and 2-8% voltage unbalance trip point.
|
 Model 201 DPDT |
The 201-XXX-DPDT is an 11-pin octal base plug-in voltage monitor designed to protect 3-phase motors
regardless of size. The 201-100-DPDT is used on 95-120VAC, 50/60Hz motors and the 201-200-DPDT is used on 190-240VAC, 50/60Hz
motors to prevent damage caused by incoming voltage problems. The units feature two isolated sets of contacts that are ideal
for use with two control circuits with different voltages.
The unique microcontroller-based voltage and phase-sensing circuit constantly monitors the voltages to
detect harmful power line conditions. This unit is also available with a shorter trip delay and faster restart delay. The
201-XXX-DPDT-60mS has a trip delay of 0.5 seconds and a restart delay of 60 milliseconds.
|
 Model 202 |
SymCom Model 202 is an auto-ranging voltage monitor designed to protect 3-phase motors regardless of size.
It is used on 190-480 VAC, 50 or 60Hz motors to prevent damage caused by incoming power problems. The Model 202-RP trips on
reverse phase only. It monitors the phase rotation of 3-phase systems. Critical applications include fan motors, scroll
compressors, grinders, conveyor systems, elevators and escalators. The status light turns green and the relay is
activated when rotation is correct.
|
 Model 202-RP |
SymCom Model 202-RP trips on reverse phase only. It monitors the phase rotation of
three-phase systems. Critical applications include fan motors, scroll compressors, grinders, conveyor systems, elevators and
escalators. The status light turns green and the relay is activated when rotation is correct.
|
 Model 250A |
SymCom Model 250A is an auto-ranging voltage monitor designed to protect 3-phase motors
regardless of size. It is used on 190-480VAC, 50 or 60Hz motors to prevent damage caused by incoming power problems.
|
 Model 250-600 |
The Model 250-600 is a three-phase voltage monitor designed to protect 500-600VAC, 50/60Hz motors
regardless of horsepower. It will protect motors from damage caused by single phasing, phase reversal, voltage unbalance,
low voltage and high voltage. Added features include DPDT contacts and an adjustable restart delay. The DPDT relay allows
control of two circuits with potentially different voltages. When a harmful condition is detected, the unit's output relay
is deactivated after a specified fixed trip delay.
|
 Model 350 |
SymCom Model 350 is a heavy duty voltage monitor. The product should be used when high current relays,
dual contacts or 480V controls are used. Since, the Model 350 uses heavy duty relays it comes in fixed voltage range models
rather than a dual auto-ranging version like the Model 250. SymCom MotorSaver Model 350-200 comes with a 15A general purpose
contact. The Model 350-400 provides a Form C (SPDT) relay rated to switch up to 600V, allowing the use of 480V controls
eliminating the need for a control power transformer to step the voltage down to 120-240V. Several two Form C (DPDT) models
are also available.
|
 Model 355 |
SymCom Model 355 3-phase voltage monitor is perfect for heavy-duty applications that need
both protection and simple user-friendly diagnostics. Applications include pump panels, commercial HVAC, oil rigs and others.
The Model 355-200 is equipped with a heavy-duty 15A general purpose SPDT relay. The Model 355-400 and 355-600 are equipped with
a 470VA @ 600VAC pilot duty SPDT relay. A high voltage (600V) DPDT relay output option is available with the 400V and 600V
models.
|
 Model 455 |
SymCom Model 455 3-phase voltage monitor combines load and line side monitoring to alert the user of
failure or impending contactor failure. The line side monitoring will protect the motor from damaging line side conditions
prior to the motor starting. With other line-load side voltage monitors, the motor must be started before a voltage problem
is detected. With the Model 455, the motor is fully protected at all times. The motor will not start when a power problem is
present.
The Model 455 automatically senses whether it is connected to a 200V, 300V system or 400V system. An
adjustment is provided to set the nominal line voltage from 190-240 or 380-480VAC. Other adjustments include a 2-30 second trip
delay, a 2-300 second restart delay (and manual restart), and a voltage unbalance trip point adjustment from 2-8%. Four LEDs
indicate the status of the Model 455: run light, undervoltage, overvoltage, and phasing fault. The Model 455 is the only load
and line side monitor on the market that does not require a separate power source for its electronics, making it much easier to
install.
|
 Informer MS |
SymCom Informer MS is a handheld diagnostic tool designed for use with MotorSaver Model
455s equipped with infrared LED transmitters. The Informer MS receives and displays MotorSaver data to assist in monitoring and
troubleshooting the system. An auxiliary kit is available which allows the Informer MS to read data from a panelmounted Model
455 without opening the panel door.
|
 Model 460 |
SymCom Model 460 is designed to protect 3-phase loads from damaging power conditions. The
460's wide operating range, combined with UL and CE compliance, enables quick access to domestic and global markets. The Model
460 automatically senses whether it is connected to a 190-240V 60Hz system, a 440-480V 60Hz system, or a 380-416V 50Hz system.
An adjustment is provided to set the nominal line voltage from 190-240 or 380-480VAC. Other adjustments include a 1-30 second
trip delay, a 1-500 second restart delay, and a 2-8% voltage unbalance trip point adjustment.
|
 Model 460-14/460-15 |
SymCom Models 460-14 and 460-15 are designed to protect 3-phase loads from damaging power
conditions. Its wide operating range, combined with UL, cUL and CE compliance, enables quick access to domestic and global
markets. The Models 460-14 and 460-15 automatically sense whether they are connected to a 190-240V 60Hz system, a 440-480V 60Hz
system, or a 380-416V 50Hz system. An adjustment is provided to set the nominal line voltage from 190-240 or 380-480VAC. Motor
control is accomplished with one NO contact and one NC contact (Model 460-14) or two NO contacts (Model 460-15).
|
 Model 460-VBM |
SymCom Model 460-VBM is designed to protect 3-phase loads from damaging power conditions.
The 460-VBM's wide operating range combined with UL and CE compliance enables quick access to domestic and global markets. The
Model 460-VBM automatically senses whether it is connected to a 190-240V 60Hz system, a 440-480V 60Hz system, or a 380-416V 50Hz
system. Adjustments are provided to set the low voltage and high voltage trip points. Other adjustments include a 1-30 second
trip delay and a 1-500 second restart delay.
|
 Model 460-400Hz |
The Model 460-400Hz is designed to protect 3-phase, 400Hz motors from damaging power conditions. The
460s wide operating range combined with UL and CE compliance enables quick access to domestic and global markets.
A unique microcontroller-based voltage and phase-sensing circuit constantly monitors the 3-phase
voltages to detect harmful power line conditions. When a harmful condition is detected, the MotorSaver's output relay is
deactivated after a specified trip delay. The output relay reactivates after power line conditions return to an acceptable
level for a specified amount of time (restart delay). The trip delay prevents nuisance tripping due to rapidly fluctuating
power line conditions. The Model 460-400Hz has an operating range from 190-480V, 400Hz.
|
 Model 460L |
The Model 460L is designed to protect 3-phase loads from damaging power conditions. The 460L's wide
operating range combined with UL and CE compliance enables quick access to domestic and global markets.
A unique microcontroller-based voltage and phase sensing circuit constantly monitors the 3-phase
voltages to detect harmful power line conditions. When a harmful condition is detected, the MotorSaver's output relay is
deactivated after a 4 second trip delay. The output relay reactivates after line power conditions return to an acceptable
level for a specified amount of time (Restart Delay). The trip and restart delays prevent nuisance tripping due to rapidly
fluctuating line power conditions. The Model 460L automatically senses whether it is connected to a 190-240VAC 60Hz system,
a 440-480VAC 60Hz system or a 380-416VAC 50Hz system. An adjustment is provided to set the nominal line voltage from
190-240VAC or 380-480VAC. Other adjustments include a 1-500 second restart delay.
|
 Model 601 |
SymCom Model 601 3-phase voltage monitor is a fully-programmable electronic voltage monitor
designed to monitor 3-phase systems. It can be used as a stand-alone product or
Networked with a RM-1000, RM-2000, PLC, computer or SCADA system. When a
harmful condition is detected, the MotorSaver's output relay is deactivated after the specified trip delay. The output relay
reactivates after power line conditions return to an acceptable level for the programmed restart delay (RD2).
The following 11 setpoints can be viewed from the 3-digit LED display or from a networked device: low
voltage, high voltage, voltage unbalance, low frequency, high frequency, trip delay for voltage/frequency faults, trip delay
for single-phase faults, rapid-cycle timer (RD1), restart delay after all faults (RD2), type of restart after all faults
(manual or automatic), and RS-485 address. Six parameters can be viewed as the motor is running: L1-L2 voltage, L2-L3 voltage,
L1-L3 voltage, average voltage, percent voltage unbalance, and frequency.
|
|
Our SymCom distributors warehouse in Boise, Idaho USA stocks some SymCom products enabling us to further
assist you in finding the correct ABB SSAC Three-Phase Voltage Monitor in the USA, Canada and Mexico. Whether we have SymCom
MotorSaver 3-Phase Voltage Monitor in stock in Boise, Idaho USA or need to ship direct from SymCom to any USA cities;
Clearwater Tech can get SymCom Microcontroller Based Motor Protectors to you fast and save you some money! It will be very
helpful if you have the SymCom MotorSaver Voltage Monitors part numbers ready, then our sales representatives can provide you
with a pricing and availability quote for SymCom 3-Phase Voltage Monitor that you are looking for in seconds. If you do not
have the part numbers for SymCom Three-Phase Voltage Monitors, our application engineers will be able to help you figure out
the part numbers and get the price quote to you as soon as possible.
|
|
|
|
 |
|
| Part Number: |
|
|
Can't find a part number?
E-mail Us! |
|
|