Clearwater Tech Logo

TURCK

Home   >   Products   >   TURCK USA   >   IM1   >   Switching   >   Intrinsically Safe   >   Amplifiers

TURCK

The MK13-UNF-Ex0/24VDC and MK13-UPF-Ex0/24VDC are single channel switching amplifiers with intrinsically safe input circuits. They are used to isolate and transfer discrete signals from a hazardous location to a non-hazardous location.

TURCK MK13-UNF-Ex0/24VDC & MK13-UPF-Ex0/24VDC Single Channel Intrinsically Safe Switching Amplifiers Distributors

MK13-UNF-Ex0/24VDC & MK13-UPF-Ex0/24VDC

Inputs are typically NAMUR sensors or dry contacts, although devices providing a variable resistance conforming to DIN 19234 may be used - e.g. variable resistors, thermistors, etc.

Each provide two short-circuit protected transistor outputs. A three-position switch on the front cover selects the output mode. Positions "A", "R" and "V" represent direct mode (N.O.), inverse mode (N.C.) and complementary mode, respectively.

The output mode is dependent on the input device.

In positions "A" and "R", output 1A follows the input signal, while the Alarm/1B output provides indication of faults in the input circuit. The Alarm/1B output remains energized during normal operation.

In position "V", the Alarm/1B output provides an output complementary to output 1A. No alarm indication is provided in position "V".

If you are looking for TURCK MK13-UNF-Ex0/24VDC & MK13-UPF-Ex0/24VDC, please call us on (800) 894 - 0412 or email us at info@clrwtr.com we will do our best to help you find the MK13-UNF-Ex0/24VDC single channel switching amplifier that you are looking for at the most competitive prices possible. If you are searching for MK13-UPF-Ex0/24VDC switching amplifiers with intrinsically safe input circuits technical information (data-sheets) please use the datasheets or product selection guide page links.

  • PNP - MK13-UPF-Ex0/24VDC
  • NPN - MK13-UNF-Ex0/24VDC

The input circuit is monitored for short-circuit and wire-break. If a fault in the input circuit occurs, both outputs are de-energized and the green LED is switched off.

When dry contacts are the input device, the input circuit monitoring function must be turned off by jumpering terminals 3-4, or resistors must be added to the switch as shown in Contact Configuration.

A yellow LED indicates switching status.

Our industrial factory automation supplies distributors warehouse in Boise, Idaho USA stocks some TURCK products enabling us to further assist you in finding the correct TURCK MK13-UNF-Ex0/24VDC in the USA, Canada and Mexico.

Whether we have TURCK MK13-UPF-Ex0/24VDC in stock in Boise, Idaho USA or need to ship direct from TURCK to any USA cities; Clearwater Tech can get MK13-UNF-Ex0/24VDC switching amplifier to you fast and save you some money!

It will be very helpful if you have the MK13-UPF-Ex0/24VDC switching amplifier part numbers ready, then our sales representatives can provide you with a pricing and availability quote for MK13-UNF-Ex0/24VDC switching amplifiers that you are looking for in seconds.

If you do not have the part numbers for MK13-UPF-Ex0/24VDC switching amplifiers, our application engineers will be able to help you figure out the part numbers and get the price quote to you as soon as possible.

Stock Check

Part No:
OR
Manufacturer:

Search Tips
Can't find a part number?
E-mail Us!

Leuze Sensors

The BCL 34 Series has a protection rating of IP 65. This unit has been designed for Profibus and is the first that has a directly integrated Profibus DP interface. It is available with two different Profibus connection modules: MS 34 103 and MS 34 105. The BCL 34 bar code reader is also available with a modular service display: MS 1 101. The laser beams are on an angle of 10 degrees to the top to avoid a total reflection of the laser

SSAC Controls

ABB FB series is a universal lamp alarm relay designed to sense the failure of flashing LED beacon lamps. It will monitor the operation of one to eight beacons connected to a single flasher and/or auxiliary modules and the operation of the flasher. The FB Series output relay energizes when one or more lamps fail. All monitored lamps must be the same wattage and voltage. The 0.5A solid-state output energizes