SmartPlug - Add Smarts To Your Sensor

TURCK 6/8/2018
SmartPlug - Add Smarts To Your Sensor

SmartPlug Makes Your Sensor or Switch "Smart" by adding  functionality to your signal output via a simple, teachable Plug and Work solution.  Add functions such as timing, counting, speed monitoring or signal inversion by simply plugging the SmartPlug into your sensor or switch.
 
Programming is done via a simple "teach" input on the existing pin #2 of your existing M12x1 (eurofast) connector. The SmartPlug works with not only TURCK sensors, but with 3-wire DC sensors from many different manufacturers. For connection to sensors using M8x1 (picofast), or 7/8-16UN (minifast) connectors, adaptor cables are available.

SmartPlugs may be combined in series to provide multiple functions, such as a speed monitor with a time delay.

SmartPlug Features:

• Add function to existing installations.
• Solve control problems quickly in the field.
• Simple plug-in installation – uses industry standard M12x1 4-pin connectors (eurofast).
• Programmed through “teach” input – Pin 2.  LED aids programming.
• All styles are 400 mA short-circuit-proof, noise immune switching amplifiers.

TURCK SmartPlug

SPC1-AP6X / SPC1-AN6X

Programmable pulse or interval counter

• Direct adaptation between sensor and connecting cable
• Counting of pulses or intervals
• Simple setting by external teach-input
• No additional wiring required
• Counting range from 0 to 65535
• Switching amplifier up to 400 mA
• N.C./N.O. inverter

TURCK SmartPlug

The SPC1 SmartPlug is a freely programmable counter for the direct adaptation to sensors with a standardized
M12x1 connection.
 
The SPC1 SmartPlug is available in 2 versions:

PNP input - PNP output SPC1-AP6X (for use with PNP sensors)
NPN input - NPN output SPC1-AN6X (for use with NPN sensors)

Connection:

The SmartPlug is very easy to connect; it is plugged onto the M12x1 connector of a sensor and the connecting cable is
connected to the other side of the SmartPlug.  The sensor configuration has to meet the standards (1+V (BN) 3 -V (BU) 4 output (BK) ).

TURCK SmartPlug

Setting:
 
The setting of the preset number is made by using the signals "teach input" and "input SmartPlug". If for example, 4 pulses have to be counted, the setting can be made as follows (operating voltage being switched on):
 
1. Connect teach input with +V.
2. Actuate the sensor 4 times (= 4 pulses) - The SmartPlug recognizes automatically 4 pulses at the "input SmartPlug".
3. Disconnect teach input from +V → READY.
 
After this setting, the output of the SmartPlug is activated every fourth pulse.  The setting is maintained when the sensor is switched off.

TURCK SmartPlug

H = input or output active;    L= input or output inactive

When switching on the operating voltage, the counting procedure is reset. The initial state of the preset number is 1 (pulse counter).

SPF1-AP6X / SPF1-AN6X

Programmable over or under speed monitor

• Direct adaptation between sensor and connecting cable
• Teachable speed limit
• Simple setting by external teach-input
• No additional wiring required
• Frequency range 0.015 Hz - 1 kHz
• Output load up to 400 mA

TURCK SmartPlug

The SPF1 SmartPlug is a frequency threshold module for the direct adaptation to sensors with a standard M12x1 connection.

The SPF1 SmartPlug is available in 2 versions:

PNP input - PNP output SPF1-AP6X (for use with PNP sensors)
NPN input - NPN output SPF1-AN6X (for use with NPN sensors)

Connection:

The SmartPlug is very easy to connect; it is plugged onto the M12x1 connector of a sensor and the connecting cable is
connected to the other side of the SmartPlug.  The sensor configuration has to meet the standards (1 +V (BN) 3 -V (BU) 4 output (BK) ).

TURCK SmartPlug

Function:

The SmartPlug SPF1 observes the frequency of the signal at the pin "input SmartPlug".  The output is activated if the setup frequency falls below approximately 5%.

Setting for under speed monitoring:

1. Set sensor up to sense object with SmartPlug SPF1 connected.  Make sure sensor is sensing properly and output is switching.
2. Move object or set rotation to nominal speed.
3. Connect +voltage +V to "Teach Input" and then disconnect (turn off) voltage +V. (Pulse +V to Teach Input,  >1 full cycle of senses object - e.g.  >1 full revolution)
4. Done, if speed or frequency drops by 5% or 95% of nominal speed, then SmartPlug is activated.

Setting for over speed monitoring:

(Note: over speed output will be inverted. i.e. output activated for normal speed & output off for over speed.)
1. Set sensor up to sense object with SmartPlug SPF1 connected. Make sure sensor is sensing properly and output is switching.
2. Move object to set rotation to 106% plus X% over speed allowance of nominal speed.
3. Connect+voltage +V to "Teach Input" and then disconnect (turn off) voltage +V. (Pulse+V to Teach Input, >1 full cycle of senses object - e.g.  >1 full revolution).
4. Done.  If speed or frequency goes above setpoint, then SmartPlug output goes off.

SPN1-AP6-ARN6X / SPN1-AN6-ARP6X

PNP/NPN or NPN/PNP converter, adjustable N.O./N.C. inverter

• Direct adaptation between sensor and connecting cable
• N.C./N.O. function adjustable
• Simple setting via external teach-input
• No additional wiring required
• Switching frequency up to 10 kHz
• Switching amplifier up to 400 mA

TURCK SmartPlug

The SPN1 SmartPlug is a switching channel convertor for the direct adaptation to sensors with a standard M12x1 connection.

The SPN1 SmartPlug is available in 2 versions:

PNP input - NPN output SPN1-AP6-ARN6X (for the conversion of PNP sensors to NPN output)
NPN input - NPN output SPN1-AN6-ARP6X (for the conversion of NPN sensors to PNP output)

Connection:

The SmartPlug is very easy to connect: it is plugged onto the M12x1 connector of a sensor and the connecting cable is
connected to the other side of the SmartPlug.  The sensor configuration has to meet the standards (1 +V (BN) 3 -V (BU) 4 output (BK) ).

TURCK SmartPlug

Function:

The SmartPlug SPN1-AP6-ARN6X converts a PNP input signal into a NPN output signal.
The SmartPlug SPN1-AN6-ARP6X converts a NPN input signal into a PNP output signal.
Additionally the signal can be inverted (N.C./N.O. function).

Setting:

The setting of the inverting function is made by means of the signals "teach input" and "input SmartPlug"

Example:

1.  Setting the SmartPlug into the inverting mode:
a)  activate sensor (output is on)
b)  connect teach input and +V and disconnect (pulse or signal to +V).  READY
2.  Setting the SmartPlug into the non-inverting mode (factory setting)
a)  inactivate Sensor (output is off)
b)  connect teach input and +V and disconnect (pulse or signal to +V).  READY
This setting is maintained when the sensor is off.

SPT1-AP6X / SPT1-AN6X

Programmable timer for on-delay time or off-delay time

• Direct adaptation between sensor and connecting cable
• Teachable as on-delay time or off-delay time
• Simple setting by external teach-input
• No additional wiring required
• Time range between 1 and 65535 ms
• Switching amplifier up to 400 mA
• Can be used as pulse stretcher

TURCK SmartPlug

The SPT1 SmartPlug is a freely programmable timer for the direct adaptation to sensors with a standardized M12x1 connection.

The SPT1 SmartPlug is available in 2 versions:

PNP input - PNP output SPT1-AP6X (for use with PNP sensors)
NPN input - NPN output SPT1-AN6X (for use with NPN sensors)

Connection:

The SmartPlug is very easy to connect: it is plugged onto the M12x1 connector of a sensor and the connecting cable is
connected to the other side of the SmartPlug.  The sensor configuration has to meet the standards (1 +V (BN) 3 -V (BU) 4output (BK) ).

TURCK SmartPlug

Setting:

The setting of the delay time is made by means of the signals "Teach input" and "Input SmartPlug".  A delay time of 4 seconds for example can be set as follows (the operating voltage being switched on):

1.  Connect teach input with +V
2.  Actuate sensor for 4 seconds
3.  Disconnect teach input from +V.  READY

After this setting the SmartPlug has a slow operation lasting 4 seconds.
This setting is maintained when the sensor is switched off.

TURCK SmartPlug

When switching on the operating voltage, the timer is reset.  The initial state of the preset time is 100 ms off-delay.
H= input/output active   L= input/output inactive