How Do I Choose Breakers And Magnets?

Fuji 3/22/2018
How Do I Choose Breakers And Magnets?Since the rated current is described below, please select according to the capacity to be used.

HD (High Duty) specification: heavy overload application
LD (Low Duty) specification: Light overload application
How Do I Choose Breakers And Magnets?
(Note) English characters are included in inverter type ?. S (basic type), E (EMC filter built-in type), H (built-in DC reactor type).
• Install MCCB and ELCB on inverter input side. It can not be installed on the inverter output side.
• For MCCB and ELCB, the recommended rated current value (MCCB, ELCB ground environment condition is selected considering ambient temperature condition correction factor (0.85)) under the condition of 50 ° C or less in board temperature. The specific format should be in accordance with the short circuit breaking capacity of the equipment.
• When selecting the MC, the type of wire to be connected is assumed to be HIV wire (75 ° C tolerance). When selecting with other wires, it is necessary to reselect it taking account of the terminal block size and wire size.
• For ELCB, it has overcurrent protection function.
• Use MCCB and ELCB rated current shown in the above table for prevention of secondary disasters when inverter breakage occurs. Please do not use MCCB, ELCB with rated current larger than necessary.

HD (High Duty) specification: heavy overload application
MD (Medium Duty) specification: medium overload application
LD (Low Duty) specification: Light overload application
How Do I Choose Breakers And Magnets?
How Do I Choose Breakers And Magnets?
* 610CM, 612CM, 616CM: Shin Aichi Electric Manufacturing Co., Ltd.
(Note) English characters are included in inverter type ?. S (basic type), E (EMC filter built-in type), H (built-in DC reactor type).
• Install MCCB and ELCB on inverter input side. It can not be installed on the inverter output side.
• For MCCB and ELCB, the recommended rated current value (MCCB, ELCB ground environment condition is selected considering ambient temperature condition correction factor (0.85)) under the condition of 50 ° C or less in board temperature. The specific format should be in accordance with the short circuit breaking capacity of the equipment.
• When selecting the MC, the type of wire to be connected is assumed to be HIV wire (75 ° C tolerance). When selecting with other wires, it is necessary to reselect it taking account of the terminal block size and wire size.
• For ELCB, it has overcurrent protection function.
• Use MCCB and ELCB rated current shown in the above table for prevention of secondary disasters when inverter breakage occurs. Please do not use MCCB, ELCB with rated current larger than necessary.