Frequently Asked Questions For Fuji Drive Frequency SettingsFrequency setting is F01 (Frequency setting 1). Please set the desired setting method.
* factory shipping setting value is F01 = 0 (Touch panel key operation).

Frequently Asked Questions For Fuji Drive Frequency Settings

Frequently Asked Questions For Fuji Drive Frequency Settings

Setting Method

Frequently Asked Questions For Fuji Drive Frequency Settings

Notes

In addition to this setting there are high-priority setting means (communication, multistage frequency, etc). For details, refer to "Control Block Diagram" in Frenic Mega User's Manual.

One Point Advice

- The voltage value to be input to the terminal [12], the current value input to the terminal [C1], the setting by the main unit volume can be set to an arbitrary range by the gain-bias setting. Detail is F18 (bias for frequency setting 1).
- The voltage value input to the terminal [12] and the current value input to the terminal [C1] can be filtered. Detail is C33 (Analog input adjustment - terminal [12] filter), and C38 (analog input adjustment - terminal [C1] filter).
- Frequency setting 1 (F01) And frequency setting 2 (C30) is switched using the "Hz 2 / Hz 1" terminal function. For the "Hz 2 / Hz 1" terminal function, E01-E09 , E98, E99. Refer to "Function selection of terminals [X1] - [X9], [FWD], [REV]".